Introduction
In industrial automation control systems, modulating electric actuators usually use 4-20mA analog signals to control valve position.Many people have a question when they first come into contact with electric actuators:
Since 0-20mA can also represent a 0%-100% control range, why is 4-20mA more commonly used in industrial applications instead of 0-20mA?
The most important reason is that 4mA provides a Live Zero, also known as an “active zero.”
Compared with 0-20mA, 4-20mA makes it easier to distinguish between a normal 0% control command and conditions such as a broken wire or serious signal abnormality. At the same time, 4-20mA has become a very mature analog signal method in industrial automation and offers good system compatibility with PLCs, DCS systems, process instruments, and modulating actuators.
It should be noted that both 4-20mA and 0-20mA are essentially current signals. Compared with voltage-type analog signals such as 0-10V, current signals are generally more suitable for long-distance analog signal transmission in industrial environments, but this is not an advantage unique to 4-20mA compared with 0-20mA.
Quick Answer: Why Do Modulating Electric Actuators More Commonly Use 4-20mA?
Modulating electric actuators more commonly use 4-20mA instead of 0-20mA mainly because 4mA provides a Live Zero.
In a typical direct-acting control setup:
- 4mA = 0% valve position
- 12mA = 50% valve position
- 20mA = 100% valve position
Even when the valve is at a 0% control command, there is still a normal 4mA current in the signal loop.
If the signal wire is disconnected or the control signal experiences a serious abnormality, the input current may drop to close to 0mA.
Therefore, the control system or an electric actuator that supports signal-loss detection can more easily distinguish between: Normal zero position and signal failure
In addition, 4-20mA has been widely used in industrial automation for a long time and offers good compatibility with PLCs, DCS systems, and various process instruments.
It should be noted that 4mA = 0% and 20mA = 100% is only a common direct-acting configuration and is not an absolute rule. Some electric actuators can also be configured with reverse-acting logic.
Table of Contents
- What Is 4-20mA? Why Is Live Zero Needed?
- How Does 4-20mA Work in a Modulating Electric Actuator?
- Why Do Industrial Systems More Commonly Use 4-20mA?
- What Should Be Confirmed When Selecting a 4-20mA Electric Actuator?
- Conclusion
- FAQ
Keywords: Electric Actuator, 4-20mA Signal, Modulating Electric Actuator, Electric Valve, Valve Control
You can quickly learn more by watching the following videos:
1. What Is 4-20mA? Why Is Live Zero Needed?
1.1 How Does 4-20mA Represent Valve Position?
4-20mA is a very common analog current signal in industrial automation.
For a modulating electric actuator, it is usually used to represent the target valve position that the actuator needs to move to.
In a typical direct-acting, linear position control setup:
| Input Signal | Target Valve Position |
|---|---|
| 4mA | 0% |
| 8mA | 25% |
| 12mA | 50% |
| 16mA | 75% |
| 20mA | 100% |
A PLC, DCS, or other control system can output a corresponding 4-20mA control signal according to process parameters such as pressure, flow, temperature, and liquid level.
After receiving the signal, the electric actuator drives the motor and adjusts the valve to the specified position.
If the actuator uses a reverse-acting configuration, the valve positions corresponding to 4mA and 20mA can also be reversed.
Important: 50% valve position does not equal 50% flow.
For example, in a typical linear position control setup:
12mA can correspond to 50% valve position.
However, this does not mean that the flow in the pipeline is necessarily 50%.
The actual flow is also affected by the following factors:
- Valve structure;
- Cv/Kv;
- Valve flow characteristics;
- Pipeline differential pressure;
- System resistance.
Therefore, 4-20mA primarily represents the target position of the actuator rather than directly representing the medium flow rate.
1.2 Why Can 0mA in a 0-20mA Signal Cause Ambiguity?
From a control principle perspective, 0-20mA can also achieve 0%-100% proportional control.
For example:
- 0mA = 0%
- 10mA = 50%
- 20mA = 100%
The problem is:
0mA may represent either a normal 0% control command or an abnormal condition in the control loop.
For example:
- Signal wire disconnection;
- Analog output interruption;
- Loose wiring terminals;
- Control loop abnormality;
- Loss of the upper-level control signal.
If the normal zero position itself is 0mA, when the control system detects 0mA, it must use other methods to determine whether it represents a normal 0% command or a signal failure.
This is the disadvantage of 0-20mA in low-end fault detection.
1.3 What Is Live Zero?
One of the most important characteristics of 4-20mA is that it uses 4mA as the Live Zero, also known as the “active zero.”
Under normal conditions, even if the control system requires the actuator to move to the 0% position, there is still a 4mA current in the signal loop.
For example: 4mA = normal 0% command
When the signal line becomes open circuit or the control signal experiences a serious abnormality, the current may drop to close to: 0mA
Therefore, the system can more easily distinguish between:
4mA: normal zero position
Close to 0mA: possible wire disconnection or serious signal abnormality
This is one of the most important advantages of 4-20mA compared with 0-20mA.

2. How Does 4-20mA Work in a Modulating Electric Actuator?
The function of a modulating electric actuator is not only to open or close a valve, but also to move the valve to different positions according to the control signal.
For example, an actuator uses a typical direct-acting configuration:
- 4mA = 0% valve position
- 12mA = 50% valve position
- 20mA = 100% valve position
When the PLC or DCS changes the output signal, the electric actuator adjusts the valve position according to the input signal.
Therefore, 4-20mA is very suitable for applications that require continuous adjustment.
2.1 4-20mA Control Input
4-20mA Input is the position command sent by the control system to the electric actuator.
Simply understood: the control system tells the actuator, “Where the valve needs to move.”
For example:
If the PLC outputs 12mA, under a typical linear configuration, the actuator can move the valve to approximately 50% of the target position.
2.2 4-20mA Position Feedback
Some automation systems not only need to control the valve, but also need to know the actual current valve position.
In this case, the following can be used: 4-20mA Position Feedback
For example:
- 4mA feedback = 0% valve position
- 12mA feedback = 50% valve position
- 20mA feedback = 100% valve position
Therefore, two concepts need to be distinguished:
Control input signal: tells the actuator “where it needs to go.”
Valve position feedback signal: tells the PLC/DCS “where it actually is now.”
Input and feedback should not be confused.

2.3 What Happens to the Actuator After Signal Loss?
If the 4-20mA control signal is suddenly lost while the actuator itself is still normally powered, and the corresponding model supports signal-loss handling functions, the actuator can perform a corresponding action according to its parameter settings.
For example:
Hold Position
Maintain the current position.
Fail Open / Open Position
Move to a preset open position.
Fail Close / Close Position
Move to a preset closed position.
Or: output a fault alarm.
The specific action should be determined according to the actuator model, control module, and the user’s process requirements.
2.4 Signal Loss Is Not the Same as Power Failure
This is an issue that is very easy to confuse in electric actuator applications.
Loss of the control signal and loss of actuator power are two different fault conditions.
If only the 4-20mA control signal is lost, but the actuator power supply remains normal and the actuator supports the corresponding signal-loss handling function, it can still operate according to the preset logic.
However, if the electric actuator itself also loses power, an ordinary electric actuator usually cannot perform a new action using only the 4-20mA signal.
If the application requires the actuator to move to a safe position after a power failure, it is necessary to confirm whether the specific product is equipped with:
- Spring return;
- Energy storage device;
- Backup power supply;
- Other dedicated power-failure safety solutions.
Therefore: Signal Loss ≠ Power Failure
4-20mA mainly solves the problem of control signal identification and cannot automatically solve the problem of actuator power loss.

3. Why Do Industrial Systems More Commonly Use 4-20mA?
The reason why 4-20mA is widely used in industrial automation can be understood from two aspects.
3.1 4-20mA Has Live Zero
This is the most direct advantage of 4-20mA compared with 0-20mA.
Because: normal 0% command = 4mA
Instead of 0mA.
Therefore, a value close to 0mA can be reserved for identifying a broken wire, open circuit, or serious signal abnormality.
For continuous production systems, this fault identification capability is very important.
3.2 Mature Industrial Compatibility of 4-20mA
After long-term industrial use, 4-20mA has become a very common analog signal method in process control.
It can be widely used with:
- PLC;
- DCS;
- Modulating electric actuators;
- Valve positioners;
- Pressure transmitters;
- Temperature transmitters;
- Flowmeters;
- Level meters;
- Other process instruments.
Therefore, when designing a complete automation control system, using 4-20mA usually makes it easier to match existing control systems and field instruments.
3.3 The Advantages of a Current Loop Are Not Unique to 4-20mA
This point needs to be clearly distinguished.
Both 4-20mA and 0-20mA are current-type analog signals.
Compared with voltage signals such as 0-10V, current loops are generally less sensitive to line resistance and voltage drop, making them more suitable for long-distance analog signal transmission in industrial environments.
However, this is: An advantage of current signals compared with voltage signals.
It is not: An advantage unique to 4-20mA compared with 0-20mA.
4-20mA further adds a 4mA Live Zero on the basis of the current loop, so compared with 0-20mA, it provides more convenient low-end fault identification.
3.4 What Is the Difference Between 4-20mA and 0-20mA?
| Comparison Item | 4-20mA | 0-20mA |
|---|---|---|
| Signal Type | Current Signal | Current Signal |
| Typical 0% Command | 4mA | 0mA |
| Typical 100% Command | 20mA | 20mA |
| Live Zero | Yes | No |
| Low-End Wire-Break Detection | Easier | Relatively Difficult |
| Industrial Process Control Applications | Very Common | Relatively Less Common |
| Modulating Actuators | Widely Used | Supported by Some Models |
Therefore, it is not that 0-20mA cannot be used.
It can also perform proportional control.
However, in industrial process control, 4-20mA uses Live Zero to solve the identification problem between “normal zero position” and “signal abnormality.” At the same time, industrial system compatibility is also more mature, so it has been more widely used.

4. What Should Be Confirmed When Selecting a 4-20mA Electric Actuator?
When selecting a modulating electric actuator in an actual application, you should not only ask:
“Does it support 4-20mA?”
The following parameters should also be confirmed at the same time.
1. Input Signal
Confirm whether it supports:
4-20mA Input
That is, whether 4-20mA can be used as the target valve position control signal.
2. Position Feedback
Confirm whether independent:
4-20mA Position Feedback
is required.
If the PLC/DCS needs to read the actual valve position in real time, it is necessary to confirm whether the actuator supports the corresponding analog feedback function.
3. Action Direction
Confirm:
Does 4mA correspond to 0% or 100%?
A common direct-acting configuration is:
4mA = 0%
20mA = 100%
However, some systems can also use:
4mA = 100%
20mA = 0%
Therefore, the signal logic should be confirmed before installation and commissioning.
4. Signal-Loss Action
Confirm what the actuator should do after the control signal is lost:
- Hold Position;
- Open;
- Close;
- Move to a preset position;
- Output an alarm.
The specific logic should be determined according to process safety requirements.
5. Power Supply & Torque
In addition to the control signal, it is also necessary to confirm:
- Actuator power supply voltage;
- Output torque;
- Valve opening and closing torque;
- Valve type;
- Valve size.
This is because 4-20mA only determines the “control method” and cannot replace the basic mechanical and electrical selection of the actuator.
6. PLC / DCS Compatibility
It is also necessary to confirm:
- Control module;
- Electrical interface;
- Input/output signals;
- Valve position feedback requirements;
- Direct/reverse action logic;
- Fault alarm requirements.
When confirming a modulating electric actuator with KST, it is recommended to provide the following information at the same time:
Valve type and size, required output torque, power supply voltage, 4-20mA input requirements, whether 4-20mA valve position feedback is required, direct/reverse action logic, and the expected action after signal loss.
The specific functions should be subject to the corresponding KST electric actuator model and control module configuration.

5. Conclusion
Modulating electric actuators more commonly use 4-20mA instead of 0-20mA. The core reason is not that 4-20mA “transmits farther,” but that 4mA provides a Live Zero.
Under normal conditions: 4mA can represent a 0% command.
When the signal line is disconnected or the signal experiences a serious abnormality: the current may drop to close to 0mA.
In this way, the control system can more easily distinguish between a normal zero position and an abnormal control signal.
At the same time, 4-20mA has been widely used for a long time in PLCs, DCS systems, process instruments, and various modulating actuators, so it offers mature industrial compatibility.
When selecting an electric actuator in an actual application, it is also necessary to confirm: 4-20mA input, valve position feedback, direct/reverse action, signal-loss action, power supply voltage, actuator torque, and PLC/DCS interface requirements.
Only by confirming both the control signal and the actuator configuration can a more stable and reliable valve automation control system be established.
6. FAQ
Q1: Does 4mA Always Mean the Valve Is Fully Closed?
No.
In a typical direct-acting control setup, 4mA usually corresponds to 0% valve position, while 20mA corresponds to 100% valve position.
However, some electric actuators can be configured with reverse-acting logic, so 4mA may also correspond to the 100% position.
The specific configuration should be determined according to the actuator parameter settings.
Q2: What Valve Opening Does 12mA Correspond To?
If standard 4-20mA linear position control is used, 12mA usually corresponds to a 50% target valve position.
However, it should be noted that 50% valve position does not equal 50% flow.
The actual flow also depends on the valve structure, Cv/Kv, differential pressure, and pipeline system characteristics.
Q3: Why May the Current Drop Close to 0mA After a Wire Break?
Because a normal 4mA signal requires a complete current loop.
When the signal line becomes open circuit, the normal current can no longer continue to flow, so the input current may drop to close to 0mA.
This is also an important reason why 4-20mA uses Live Zero to help identify wire-break faults.
Q4: Can an Electric Actuator Use 0-20mA?
Yes.
Some modulating electric actuators can support:
- 0-20mA;
- 4-20mA;
- 0-10V;
- Other analog input methods.
The specific signals supported should be confirmed according to the actuator control module and product specifications.
Q5: Do All Electric Actuators Need 4-20mA?
No.
If the electric actuator only needs to control the valve: fully open / fully closed
On/off control can usually be used.
If the application requires continuous adjustment of the valve position according to process parameters such as pressure, flow, temperature, and liquid level, then 4-20mA or another analog control method is usually selected.