Introduction
In industrial automation systems, both solenoid valves and motorized valves can control fluid flow through electrical signals, but their driving methods and application scenarios are different.
The most fundamental difference between a solenoid valve and a motorized valve lies in their driving methods. A solenoid valve uses an electromagnetic coil to directly actuate the valve core or control the main valve through a pilot mechanism. In contrast, a motorized valve primarily uses an electric motor and transmission mechanism to open, close, or adjust the valve position.
Conventional on/off solenoid valves are typically used for rapid shutoff or flow path switching, while motorized valves can provide both on/off control and valve position adjustment through modulating electric actuators. It should be noted that some proportional solenoid valves also have regulating capabilities.
So, how should you choose between them in practical engineering applications? This article mainly compares conventional on/off solenoid valves used for process media with motor-driven valves. It explains their differences in terms of working principles, control functions, operating differential pressure, power failure behavior, and practical applications to help you better understand these two types of valves.
Quick Answer
Although both solenoid valves and motorized valves can achieve automatic control through electrical signals, they differ significantly in driving methods, valve structures, operating differential pressure, and control functions.
Conventional on/off solenoid valves are commonly used for rapid shutoff and flow path switching, while motorized valves can provide on/off control, valve position adjustment, and valve position feedback depending on the actuator configuration. Some proportional solenoid valves can also be used for specific regulating tasks.
Therefore, when selecting a valve, you should not focus only on response speed or PLC compatibility. Instead, you should consider the medium, flow rate, operating differential pressure, control method, and expected valve state after power failure.
Keywords: Solenoid Valve vs Motorized Valve, Solenoid Valve, Motorized Valve, Electric Actuated Valve, Valve Position Feedback
1. How Do the Driving Principles of Solenoid Valves and Motorized Valves Differ?
Although both solenoid valves and motorized valves can receive electrical control signals, they convert electrical signals into mechanical movement in different ways.
1.1 Working Principle of a Solenoid Valve
A solenoid valve is an automatic control valve that uses electromagnetic force to control fluid shutoff or flow path switching.
When the electromagnetic coil receives an electrical signal, it generates a magnetic field that moves the internal valve core or pilot mechanism, thereby changing the fluid flow path.
Depending on their structure, common solenoid valves can be classified into direct-acting and pilot-operated types.
- Direct-Acting Solenoid Valve: Uses electromagnetic force to directly move the valve core. Some models are suitable for zero differential pressure applications.
- Pilot-Operated Solenoid Valve: Uses electromagnetic control together with the medium’s differential pressure to operate the main valve. Some models require a minimum operating differential pressure.
- Proportional Solenoid Valve: Can provide proportional regulation within a certain range when used with a dedicated controller, rather than being limited to simple fully open or fully closed operation.
For conventional on/off solenoid valves, energizing or de-energizing the coil is usually sufficient to make the valve perform the corresponding action according to its structural design.
Therefore, solenoid valves are commonly used in automatic water supply systems, equipment flow path switching, and control systems requiring rapid opening and closing.
It should be noted that three-way or five-way solenoid valves used to control the air supply and exhaust of pneumatic actuators are generally components of pneumatic control circuits. They perform different functions from electric ball valves or electric butterfly valves installed directly in process pipelines and cannot be considered directly interchangeable products.

1.2 Working Principle of a Motorized Valve
A motorized valve (Motorized Valve / Electric Actuated Valve) is an automatic control valve driven by an electric actuator.
Unlike a solenoid valve, a motorized valve mainly relies on an electric motor and internal transmission mechanism to drive the valve stem, thereby changing the valve’s open or closed state or its opening position.
Common types of motorized valves include:
- Electric Ball Valve

- Electric Butterfly Valve

- Electric Control Valve

For example, when the control system sends an opening command to an electric ball valve, the electric actuator rotates the ball, gradually opening the valve.
When a modulating electric actuator is used together with a valve suitable for regulation, the valve can also move to a specified position according to the control signal.
However, not all motorized valves support continuous regulation. In practical applications, the appropriate product should be selected based on the actuator type, valve structure, and control requirements.

2. What Are the Main Differences Between Solenoid Valves and Motorized Valves?
After understanding their working principles, let’s compare these two types of valves from the perspective of practical engineering selection.
2.1 Solenoid Valve vs Motorized Valve Comparison Table
| Comparison Item | Conventional On/Off Solenoid Valve | Motorized Valve |
|---|---|---|
| Driving Method | An electromagnetic coil directly controls the valve core or operates it through a pilot mechanism. | An electric motor drives the valve stem through a transmission mechanism. |
| Control Function | Mainly used for shutoff or flow path switching. | On/off control or position regulation, depending on the configuration. |
| Response Speed | Many models operate relatively quickly. | Usually requires a relatively longer operating time. |
| Operating Differential Pressure | Some pilot-operated models have minimum differential pressure requirements. | Valve differential pressure limits and actuator torque must be verified. |
| Control and Feedback | Conventional models mainly provide on/off control, with feedback depending on the model. | Can be configured for on/off control, analog modulation, and valve position feedback. |
| Power Failure State | Determined by normally open, normally closed, latching, or other structural designs. | Depends on the actuator and safety action configuration. |
| Power Consumption Characteristics | Depends on coil power, duty cycle, and holding method. | Depends on motor operation, standby power, and control module consumption. |
The above is a general comparison. Specific performance should be confirmed according to the product’s technical specifications.


2.2 Differences in Driving Methods and Response Speed
First, the most direct difference between the two is their driving method.
A solenoid valve uses electromagnetic force to control the valve core or pilot mechanism. Many conventional on/off solenoid valves can complete their actions in a short time, and some models can achieve millisecond-level response.
A motorized valve, on the other hand, requires an electric motor and transmission mechanism to drive the valve stem, so it usually takes a relatively longer time to operate.
However, operating time is not the only criterion for evaluating valve performance.
For example, solenoid valves may be more suitable for automated equipment requiring rapid switching. In contrast, motorized valves may better meet the requirements of pipeline systems that need to operate industrial ball valves, butterfly valves, or control intermediate valve positions.
The actual operating speed should be determined according to the product model, stroke, and operating load.
2.3 Differences in Control Functions and Valve Position Feedback
In terms of control functions, conventional on/off solenoid valves generally switch flow paths by energizing or de-energizing the coil.
In comparison, motorized valves can provide different control functions depending on the actuator configuration.
For example:
- On/Off Motorized Valve: Mainly used for fully open or fully closed control.
- Modulating Motorized Valve: Can adjust the target valve position according to an input signal.
- Motorized Valve with Feedback Module: Can provide valve position or status information to the control system.
For a modulating electric actuator configured with a direct linear valve position relationship, a 4–20mA control signal can correspond to a target valve position of 0%–100%.
For example, 12mA can correspond to a target valve position of 50%.
However, it is important to note that 50% valve opening does not mean 50% of the actual flow rate. The actual flow rate is also affected by factors such as the valve’s flow characteristics and system differential pressure.
In addition, not all electric actuators support continuous valve position feedback by default. Whether 4–20mA feedback, open/close limit feedback, or fault alarms are required should be confirmed during selection.
For more information about how 4–20mA signals work, you can refer to KST’s technical article:
Why Do Electric Actuators Use 4–20mA Signals Instead of 0–20mA?
2.4 Differences in Operating Differential Pressure and Flow Requirements
In addition to control functions, operating differential pressure is another factor that is easily overlooked when selecting a solenoid valve or motorized valve.
For solenoid valves, different structures have different differential pressure requirements.
For example, some pilot-operated solenoid valves rely on the medium’s differential pressure to help operate the main valve. If the system differential pressure falls below the minimum value specified by the product, the valve may not function properly.
However, this does not mean that all solenoid valves require a minimum operating differential pressure. Some direct-acting solenoid valves can be used in zero differential pressure applications.
Motorized valves are also subject to operating differential pressure limitations.
As the differential pressure changes, the torque required to open or close the valve may also change. Therefore, when selecting an electric actuator, the valve structure, operating differential pressure, and required output torque must be considered together.
In addition, regardless of which type of valve is used, the following factors should be confirmed:
- Medium type and operating temperature
- Minimum and maximum operating differential pressure
- Pipeline size and connection type
- Required flow rate or Cv/Kv value
Therefore, it is incorrect to assume that motorized valves are not affected by differential pressure limitations, or to apply the operating conditions of one type of solenoid valve to all models.
2.5 Differences in Valve State After Power Failure
In industrial automation systems, the valve state after a power supply interruption is just as important as normal opening and closing operations.
What Happens to a Solenoid Valve After Power Failure?
This depends on the specific structure of the solenoid valve.
For example, some normally closed solenoid valves return to the closed position after power loss, while normally open solenoid valves may return to the open position. The operating behavior of latching or other special designs must be confirmed separately.
Therefore, it should not be assumed that all solenoid valves automatically close after power failure.
What Happens to a Motorized Valve After Power Failure?
For a conventional electric actuator, if the power supply is interrupted, the motor usually cannot continue driving the valve according to control commands.
However, this does not mean that all motorized valves will automatically remain in their current position, nor does it mean that they can move to the fully open or fully closed position on their own.
If the system requires the valve to move to a specified safe position after power failure, it is necessary to confirm whether appropriate return mechanisms, energy storage, or backup power solutions are provided.
In addition, loss of power supply and loss of control signal are two different situations.
When the power supply is normal but the control signal is lost, some modulating electric actuators can perform a predefined action according to their settings. However, when the power supply is interrupted, whether the actuator can still complete a safety action depends on its actual hardware configuration.
For applications with special safety requirements, such as petrochemical and natural gas systems, the valve states under both abnormal conditions must be confirmed in advance.
2.6 Differences in Power Consumption and Operating Methods
Solenoid valves and motorized valves also differ in energy consumption, but it is not possible to simply conclude that one is always more energy-efficient than the other.
The power consumption of a conventional solenoid valve depends on its rated coil power, energization duty cycle, and control method. Some models require continuous energization to maintain their state, while certain latching or energy-saving models use different operating methods.
The energy consumption of a motorized valve depends on factors such as motor running time, standby power, and internal control modules.
In some electric actuators, the motor can stop running after reaching the target position, but this does not mean that the entire device consumes no electricity.
Therefore, for systems requiring frequent operation or long-term maintenance of a specific valve state, energy consumption should be compared based on actual operating frequency, holding method, and product power consumption data, rather than judging only by valve type.
3. How to Select the Right Valve for Actual Operating Conditions, and When Can They Not Be Directly Replaced?
After understanding the differences between these two types of valves, practical selection must also consider the specific operating conditions.
Both solenoid valves and motorized valves can be connected to PLC or DCS systems for remote automatic control. Therefore, the need for PLC integration is not the only factor that determines which type of valve should be selected.
The key considerations are the control task, fluid parameters, valve structure, and system safety requirements.
3.1 Which Valve Should You Choose If Only On/Off Control Is Required?
If the system only needs to open and close fluid flow, both types of valves may meet the requirements.
For example, in automatic water replenishment equipment, a conventional on/off solenoid valve may be a suitable option if the pipeline size, medium, temperature, flow rate, and operating differential pressure all meet the product requirements.
In some industrial main pipelines, if existing ball valves or butterfly valves need to be operated automatically, a compatible electric actuator can be selected according to the valve structure, connection dimensions, and operating torque.
Therefore, even when the control objective is simply to open or close the valve, the differences in installation methods, valve structures, and applicable operating conditions should not be overlooked.
3.2 How Should You Choose a Valve for Continuous Flow Regulation?
If the system needs to continuously adjust the flow rate according to production requirements, valve selection should not be based only on whether the valve can open and close.
For example, in water treatment or industrial flow control systems, a PLC or DCS can adjust the target position of a modulating motorized valve based on feedback data from a flow sensor.
The basic control process is as follows:
Flow Setpoint → PLC/DCS Controller → Modulating Electric Actuator → Control Valve → Flow Change → Flow Sensor Feedback → PLC/DCS Controller

By continuously comparing the setpoint with the actual measured value, the control system can adjust the valve position to maintain the flow rate within the required range.
However, the final regulation performance also depends on the valve’s flow characteristics, operating differential pressure, actuator performance, and control parameters.
In addition, some proportional solenoid valves can also be used for specific flow regulation tasks. Therefore, selection should be based on the regulating range, accuracy, response speed, and medium conditions, rather than assuming that all solenoid valves can only perform on/off control.
3.3 How Are Solenoid Valves and Motorized Valves Connected to a PLC?
Both types of valves can work with a PLC, but the actual connection method depends on the control function and equipment configuration.
Conventional On/Off Solenoid Valve
A PLC usually controls the energization or de-energization of the solenoid valve coil through a digital output module, relay, or suitable driving interface.
The basic control process is:
PLC Digital Output → Solenoid Valve Coil → Valve Core Movement
During actual wiring, the coil voltage, current, and electrical protection requirements must also be confirmed.

Motorized Valve
For an on/off motorized valve, the PLC can send opening or closing commands through corresponding digital control signals.
If the electric actuator is equipped with limit feedback functions, the PLC can also obtain fully open or fully closed status information.
For modulating motorized valves, control signals such as 4–20mA or 0–10V can be used to adjust the target valve position, depending on the actuator configuration.
Therefore, when designing an automation system, it is recommended to confirm the control signal, rated power supply, driving interface, and valve position feedback requirements in advance to ensure compatibility between the valve and the PLC system.

3.4 Can a Solenoid Valve Directly Replace a Motorized Valve?
The answer is: Replacement may be considered through reselection in certain applications, but the two types of valves generally cannot be directly interchanged.
If the system only requires simple on/off control, and both valve types can meet the flow rate, differential pressure, medium, and installation requirements, they may be considered as alternative options.
However, special attention is required in the following situations.
| Actual Operating Condition | Selection Recommendation |
|---|---|
| Rapid shutoff or flow path switching | Give priority to evaluating conventional on/off solenoid valves that meet the operating requirements. |
| Automation retrofit of existing ball valves or butterfly valves | Evaluate a compatible electric actuator and installation interface. |
| Continuous valve position regulation | Evaluate modulating motorized valves and compare proportional solenoid valves when necessary. |
| Zero or low differential pressure applications | Check the minimum operating differential pressure requirements of the solenoid valve. |
| Continuous valve position feedback required | Confirm the corresponding position sensor or feedback module. |
| Fail-safe action required after power failure | Verify the valve’s power failure state and safety action configuration. |
It is particularly important to note that when replacing a valve, you must check not only the maximum allowable operating pressure but also the minimum operating differential pressure and required Cv/Kv value.
For some pilot-operated solenoid valves, insufficient system differential pressure may prevent proper operation. For motorized valves, it is necessary to confirm the valve’s allowable differential pressure and whether the actuator can provide sufficient output torque.
In addition, if the existing automation system already includes continuous valve position feedback, fault alarms, or signal-loss action functions, these functions must be reconfirmed when replacing the valve.
Therefore, the fact that both types of valves can receive electrical signals does not mean that they can be directly substituted for each other.
4. FAQ
Q1: Which Responds Faster, a Solenoid Valve or a Motorized Valve?
In general, many conventional on/off solenoid valves respond relatively quickly, and some models can achieve millisecond-level response.
Motorized valves require an electric motor and transmission mechanism to drive the valve, so their operating time is usually relatively longer.
However, the actual speed still depends on the product model, stroke, and operating load.
Q2: Can Both Solenoid Valves and Motorized Valves Be Connected to a PLC?
Yes.
Conventional on/off solenoid valves are usually controlled through PLC digital outputs and suitable driving interfaces, while motorized valves can use digital, analog, or other compatible control methods depending on the actuator configuration.
Therefore, both can be used for remote automatic control.
Q3: Can All Solenoid Valves Only Perform On/Off Control?
No.
Conventional on/off solenoid valves are mainly used for shutoff or flow path switching, but proportional solenoid valves can provide proportional regulation within a certain range when used with a dedicated controller.
The specific regulating capability should be determined according to the product structure and technical specifications.
Q4: Can a Motorized Valve Stop at 50% Opening?
Yes, but an electric actuator that supports intermediate position control must be selected.
For example, a modulating electric actuator can adjust the valve to a specified position according to the control signal.
However, a target valve position of 50% does not mean that the actual flow rate is 50% of the maximum flow rate.
Q5: Will a Solenoid Valve Always Close After Power Failure?
Not necessarily.
The valve state after power failure depends on its specific structure, such as normally open, normally closed, or latching designs, as well as the product’s operating conditions.
Similarly, conventional motorized valves should not be assumed to have automatic return functions after power failure. If a safety action is required, the corresponding configuration must be confirmed according to the specific model.
Q6: Which Is More Energy-Efficient, a Solenoid Valve or a Motorized Valve?
There is no universal answer.
The power consumption of a solenoid valve depends on coil power, energization duty cycle, and holding method. For motorized valves, motor operating power, standby consumption, and control module power consumption must be considered.
The comparison should be based on valve operating frequency and actual operating time.
Q7: Can a Solenoid Valve Be Installed Directly in Place of an Existing Electric Ball Valve?
They cannot be directly interchanged simply because they serve a similar purpose.
First, it is necessary to confirm whether both types of valves can meet the same medium, flow rate, differential pressure, and control requirements.
Second, installation dimensions, connection methods, control signals, and operating requirements under abnormal conditions must also be checked.
If the goal is simply to convert an existing manual ball valve to automatic control, it is usually more appropriate to first evaluate the installation of a compatible electric actuator.